Circulair (Circular Air Balancing Damper)

Key Features

  • Manual control
  • New handle has the facility to fit an anti tamper locking screw
  • Extended bracket for standard or 50mm insulated ductwork
  • Common casing depth of 200mm
  • Eurovent duct sizes: 100-355mm dia
  • Stock Item
  • Casing leakage conforms to HVCA ductwork specification
  • DW144 Class C up to 1000Pa
  • Damper spigots conform to BSEN1506

Contact Us

Circulair dampers are circular air balancing dampers designed for inclusion into normal dry filtered air distribution systems

Actionair Circulair Air Balancing Dampers comprise of a single 1.2 mm galvanised steel blade housed within a 0.8 mm galvanised steel casing.

 

Complete with New Manual Control

The Manual Control will be suitable for uninsulated and insulated ductwork up to 50mm and have the facility to fit an anti-tamper locking screw. Our Circulair also has the facility to fit an anti tamper locking screw - the suggested screw for this is a No.4 (2.9mm) pan head self-tapping screw 8mm long. (To be supplied by others).

 

Technical and Sizing

Max Pa & Velocity

The Circulair Air Balancing Dampers are for low to medium pressure systems up to 1000Pa with a maximum air velocity of 12.5m/s

Operating Temperature

The Circulair Air Balancing Dampers should only be used in normal ducted systems, with operating temperature between 0˚C to +70˚C

Available in the following sizes

Nominal duct sizes of 100mm, 125mm, 150mm, 160mm, 200mm, 250mm, 300mm, 315mm, 350mm and 355mm (Actual sizes are in accordance with BS EN 1506: 1998)

circulair sizing.png

Circulair Construction

Blade - 1.2mm galvanised steel Blade Casing - 0.8mm galvanised steel casing Drive Shaft - Galvanised steel Control Handle - Nylon 6