Hydropac - Waterside control fan coil units
Fully insulated with
Class ‘O’ open cell
thermal and acoustic
foam.
Flush panel extra rigid construction.
Low noise levels.
Eleven speed transformer.
Full acoustic and thermal
insulation.
Various filter options.
Outputs available up to
6.4kW cooling and 6.9kW
heating.
|
|
| |
|
Actionair
Hydropac
Waterside control fan coil units - 170mm & 230mm Deep
|
|
Actionair Hydropac horizontal ceiling void mounted type fan coils are
waterside control, suitable for operation against moderate duct
resistances, using chilled water cooling medium and low pressure
Temperature control is by means of modulating 4 – port diverting
valves on heating and cooling, operated via stand alone or BMS
temperature controller and room or return air sensor. Designated ‘PHW’,
the series consists of standard 230mm deep and slimline 170mm deep
versions.
For more information including
dimensional and installation data please view the 12 page Hydropac
Catalogue
|
|
| |
|
Construction Hydropac
|
|
Catalogue
|
|
Specification for HYDROPAC
Chassis
Manufactured from 1.2mm galvanised sheet steel with 1.6mm fan decks
and back plates. The chassis shall incorporate recessed, slotted
mounting points for drop-rods. An integral acoustically lined discharge
plenum fitted with spun steel spigots and insulated blanking plates.
Access
Access to fans shall be via an insulated bottom panel with keyhole
slots.
Insulation
100Kg/m3 density, class ‘O’ CFC and HFC free open cell
foam shall be utilised for both thermal
acoustic insulation.
Fans/Motors
Fan/motor shall be permanent split capacitor external rotor ,forward
curved centrifugal type, with high efficiency, low noise multiblade
galvanised sheet steel impellers. Electrical supply shall be 230V
1ph 50Hz.
Speed Control
Speed control shall be by means of a multi-tapped transformer giving
eleven settings. A panel mounted three speed switch with additional
Fine adjustment. On/off control to fans shall be by means of a panel
mounted illuminated two position switch.
Coils
Coil matrix blocks shall be copper with aluminium fins. Fitted with
vents and drains as standard
Condensate Tray
Condensate trays shall be synthetically treated, galvanised sheet
steel, foam insulated. A positive fall to drain shall be provided
with 3/4" B.S.P. female bottom connection.
Filters
Filters shall be washable EU3, continuous filament media.