Enviropac - Energy efficient fan coils using EC fan technology
Flush panel extra rigid construction.
Low noise levels.
0-10V Fan Input
Full acoustic and thermal
insulation.
Minimal fan heat.
Various filter options.
Outputs available up to
6.4kW cooling and 6.9kW
heating.
Constant volume option.

|
|
| |
|
Actionair
Enviropac
Energy efficient fan coils using EC fan technology
|
|
Actionair Enviropac horizontal ceiling void mounted type fan coils
are waterside control, suitable for operation against moderate
duct
resistances, using chilled water cooling medium and low pressure
Temperature control is by means of modulating 4 – port diverting
valves on heating and cooling, operated via stand alone or BMS
temperature controller and room or return air sensor. Designated ‘EHW’,
the range consists of six size options at 230mm deep.
For more information including
dimensional and installation data please view the Enviropac
Datasheet
|
|
| |
|
Construction Environpac
|
|
Catalogue
|
|
Specification for ENVIROPAC
Chassis
Manufactured from 1.2mm galvanised sheet steel with 1.6mm fan decks
and back plates. The chassis shall incorporate recessed, slotted
mounting points for drop-rods. An integral acoustically lined discharge
plenum fitted with spun steel spigots and insulated blanking plates.
Access
Access to fans shall be via an insulated bottom panel with keyhole
slots.
Insulation
100Kg/m3 density, class ‘O’ CFC and HFC free open cell
foam shall be utilised for both thermal
acoustic insulation.
Fans/Motors
Fan/motor shall be LOW ENERGY EC
(Electonically commutated) external rotor ,forward curved centrifugal
type, with high efficiency, low
noise
multiblade
galvanised sheet steel impellers. Electrical supply shall be 230V
1ph 50Hz. Meets current EMC emissions and harmonic regulations.
Speed Control
Speed control shall be by means of a stepless potentiometer or 0-10v
input via BMS. On/off control to fans shall be by means of a panel
mounted illuminated two
position
switch.
Coils
Coil matrix blocks shall be copper with aluminium fins. Fitted with
vents and drains as standard
Condensate Tray
Condensate trays shall be synthetically treated, galvanised sheet
steel, foam insulated. A positive fall to drain shall be provided
with 3/4" B.S.P. female bottom connection.
Filters
Filters shall be washable EU3, continuous filament media.
Please click here to copy the specification to your clipboard ready to paste into your project specification.