Actionair Fire and smoke damper installation guides
Actionair Catalogues



Fully insulated with Class ‘O’ open cell thermal and acoustic foam.



Flush panelled extra rigid construction.

Low noise levels (down to NR25).

External resistances up to 80 Pa (Series PHW and PHA).

Easily removable condensate tray with fall to drain.

Externally mounted, ventilated control enclosure with illuminated on/off switch, and 3 speed selector switch.

Nine speed tapped transformer with pure sine wave fine adjustment for accurate commissioning.

High density class ‘O’ CFC and HFC free acoustic and thermal insulation.

Integral, multi-spigot, acoustically lined discharge plenum. (Series PHW & PHA)


 
 

Actionair Aeropac (Series PHA)
Airside control fan coil units - 230 mm Deep


Actionair Aeropac horizontal ceiling void mounted type fan coils are airside control, similar in application to the Hydropac range, but incorporate a Zone Regulating Module (ZRM) to divert air through heating, by-pass and cooling zones to control the temperature output.

The unique patented tri – lateral aerofoils allow a constant volume of air to pass throughout their operation and provide a complete seal when closed, ensuring good control and maximum operating economy with silent operation. Designated ‘PHA’, the series consists of a standard 230mm deep version.


 

Construction Aeropac

Catalogue


Specification for AEROPAC


Chassis

Manufactured from 1.2mm galvanised sheet steel with 1.6mm fan decks and back plates. The chassis shall incorporate recessed, slotted mounting points for drop-rods. An integral acoustically lined discharge plenum fitted with spun steel spigots and insulated blanking plates.

Access

Access to fans shall be via an insulated bottom panel with keyhole slots.
Insulation
100Kg/m3 density, class ‘O’ CFC and HFC free open cell foam shall be utilised for both thermal
acoustic insulation.

Fans/Motors

Fan/motor shall be permanent split capacitor external rotor ,forward curved centrifugal type, with high efficiency, low noise multiblade galvanised sheet steel impellers. Electrical supply shall be 230V 1ph 50Hz.

Speed Control

Speed control shall be by means of a multi-tapped transformer giving eleven settings. A panel mounted three speed switch with additional Fine adjustment. On/off control to fans shall be by means of a panel mounted illuminated two position switch.

Coils

Coil matrix blocks shall be copper with aluminium fins. Fitted with vents and drains as standard.

Condensate Tray
Condensate trays shall be synthetically treated, galvanised sheet steel, foam insulated. A positive fall to drain shall be provided with 3/4" B.S.P. female bottom connection.

Filters

Filters shall be washable EU3, continuous filament media.

Please click here to copy the specification to your clipboard ready to paste into your project specification.
 
   

 

Click to see Actionair Fancoil i-drop library and drop drawings into your Autodesk application with “Download idrop indicator”

To learn more about i-drop technology click here.

 


 

Our Mission
Actionair, as part of Ruskin Air Management Limited, is committed to providing innovative solutions for smoke control and waterside control fan coil units through the pursuit of excellence.
Home | Search | Products | Catalogues | Contact
Copyright © 2004
actionair. All Rights Reserved
RAM | Air Diffusion | Naco | Minimum system requirements | Legal