Actionair Fire and smoke damper installation guides


Smoke Shaft Ventilation System
 
 

Actionair Smoke Shaft Ventilation System
Series SSV


The growing demand for multi storey apartment, hotels and flats requires safe evacuation of smoke and toxic gases within the stairwell and corridor area to allow time for the safe evacuation of the occupants.

Smoke Shaft Ventilation PTC™ dampers have been designed for installation within the smoke evacuation risers in multi storey buildings.

SSV series dampers will give up to 1.56m² free area for the evacuation of smoke and toxic gases within the stairwell lobby and corridor areas of the building.

 

Construction Smoke Shaft

Catalogue

Grille Materials
Extruded Aluminium frame with 51mm border flange.

Frames/Borders
51mm Frame borders are supplied as standard with the SSV damper, optional 25mm borders available.

Grille Finish
Depending on size standard finish is either stove enamel silver RAL9006 or White RAL9010 (20% gloss) or Polyester powder, other finishes available.


For more information including dimensional and installation data please view the 8 page Smoke Shaft Ventilation System Catalogue

Model ECG
Egg Crate Grille.

Model GN Bar Grille with either 0°, 15°, or 30° blade.

Fixings

Models
Frames can be supplied either with or without a flange return, depending on the fixing arrangements suitable for the builders opening.

Grille Fixings
Grilles are prepared with countersunk screw holes in the flange to suit size 8 screws (by others).

Damper Fixings
Dampers should be secured using suitable M6/M8 fire rated anchors at 200mm CTRS to secure the damper sleeve to the wall structure. (Drillings and anchors by others).
 






 


Smoke Shaft Ventilation System Series SSV
Acrobat (PDF) Version

PDF Download Size = 640kb

 

Features

  • Smoke Management and Fire Dampers operational up to 2 hours.
  • Halogen free low smoke and fume cabling supplied as a standard feature.
  • Low closed blade leakage.
  • Dampers when closed are compliant to BS476 Part 20 Fire Damper Test Standard.
  • The control mode/damper connection shall be by means of the Unique snaplock™ reverse mounted drive interface ensures a non-obstructive installation into the builders opening.
  • Aesthetic finished Grille options.

    For more information including dimensional data please view the Smoke Shaft Ventilation System Catalogue
 

Specification

 

Specification for Smoke Shaft Ventilation System (Series SSV)

Proportional Torque Control (PTC™)
Automatic Smoke Release Dampers with 75mm x 0.5mm thick stainless steel aerodynamic interlocking blades incorporating synthetic seal, with steel blade end bearings and peripheral gasketting. Housed in a galvanised steel fully welded casing with either a flanged or flangeless sleeve for Grille connection. The control mode/damper connection shall be by means of the snaplock™ drive interface mechanism, which is reverse mounted so as not to obstruct installation into the builders opening..

Please click here to copy the specification to your clipboard ready to paste into your project specification.

Smoke Shaft Ventilation System Series SSV, as supplied by Actionair


 

 
Our Mission
Actionair, as part of Ruskin Air Management Limited, is committed to providing innovative solutions for smoke control and waterside control fan coil units through the pursuit of excellence.
Home | Search | Products | Catalogues | Contact
Copyright © 2008
actionair. All Rights Reserved
RAM | Air Diffusion | Naco | Minimum system requirements | Legal